	Capacitor display failure (fault indicator is on) 
 answer:
 1. The product voltage phase loss will cause capacitor failure (total compensation for double-stage E-1, G-1, total anti-harmonic report E-1);
 2, the product itself is damaged:
    (1) When the working voltage of the product is higher than 120% of the standard voltage of the power grid, the capacitor is prone to failure;
    (2) The harmonic content of the power grid is too high, and the reactor of the ordinary capacitor or the anti-harmonic capacitor is not properly selected, which may cause the product to be easily damaged;
 3, poor communication line wiring, communication confusion, will lead to capacitors "false positive error."